Lider Busbar Bakır Üretici

As a manufacturer of busbar copper, our production process, size design and selection criteria are directly related to the safety and efficiency of the power distribution system. From the production process optimization, size selection science, performance verification system and other dimensions  to provide a systematic reference for engineering design.

First, the busbar copper row production process

Modern busbar copper production has formed a standardized process, covering raw material handling, processing molding, surface treatment of the three major links (see Figure 1). Take Hubei Ruineng Electric as an example, its core process includes:

  1. Raw material screening: T2 electrolytic copper with purity ≥99.95% is used, and the copper content and impurity ratio are detected by spectral analyzer to ensure that the conductivity is ≥58MS/m (IACS standard);
  2. Precision processing:
    • Cutting process uses laser cutting machine to control the tolerance ≤±0.1mm, avoiding the burr problem caused by traditional punching and shearing;
    • The bending process uses a three-point hydraulic bending machine with a bending radius of 2.5-5 times the width to ensure that there are no cracks at the bending corners (GB/T 5585.1-2018);
  3. Surface treatment: the thickness of the tin-plated layer is controlled at 8-12μm, which not only improves the oxidation resistance (salt spray test ≥ 720h), but also limits the increase in contact resistance to less than 7%.

Comparison of copper processing equipment

Equipment Type Accuracy Level Başvuru Efficiency Enhancement
Conventional Punch Press ±0.5mm  Low Precision Mass Production Benchmark
CNC Bending Machine ±0.1mm Complex shaped parts processing 300%
Automatic Tinning Line Uniform Plating Products with High Corrosion Protection Requirements 200%

Second, dimensional design of bubar copper:

  • Load capacity calculation
    According to IEC 61439 standard, the formula of current-carrying capacity is:
  • ( K ): heat dissipation coefficient (1.1 for vertical, 1.0 for flat)
  • ( S ): cross-sectional area (mm²)
  • ( ΔT ): allowable temperature rise (usually taken as 55K)
  • ( ρ ): resistivity (0.01774Ω-mm²/m)

Copper row current-carrying capacity (ambient temperature 35℃)

Specification (mm Flat discharge current

-carrying capacity (A)

Vertical discharge current

-carrying capacity (A)

Cross-sectional area (mm²)
30×4 475 520 120
60×6 1069 1125 360
100×10 2121 2310 1000

third,  Digital Transformation of Performance Verification System

  1. Mechanical performance testing:
    • Tensile strength ≥295MPa (China Steel National Inspection cases show a pass rate of 99.8%)
    • Brinell hardness HB≥80 to ensure the stability of installation.
  2. Electrical test:
    • Insulation resistance ≥ 20MΩ (2500V withstand voltage test)
    • Temperature rise test: 2000A copper row under full load temperature rise ≤ 55K
  3. Environmental simulation:
    • Humidity and heat cycle test (85 ℃ / 85% RH) 1000 hours after the insulation performance degradation < 5%

Fourth, industry application scenarios Customized development according to the special needs of application scenarios:

  1. Yeni enerji alanı:
    • Battery pack connecting row adopts 0.2mm ultra-thin insulation layer, and the voltage resistance level is increased to 3000V.
    • Seismic design through GB/T 31467.3 standard (random vibration 27.8m/s²)
  2. High-voltage switchgear:
    • The 10kV system prioritizes the use of vertically placed 80×8mm specifications, and the current-carrying capacity has been increased by 18%

What is the technology for our busbar copper?

  1. Application of recycled copper: new refining technology makes the purity of recycled copper up to 99.9% and reduces carbon emission by 40%.
  2. Intelligent monitoring system: implanted RFID chip real-time monitoring of temperature, deformation, early warning accuracy>95%.
  3. Modular design: standard connectors library reduces installation time by 15% (Siemens case).